Product Features
NOTICE
Although Emergency run fulfills the functionality requirements of Fire mode, Danfoss does not recommend its use in
situations that require testing and/or compliance with specific standards as it is not certified.

5.11 Auxiliary Trip Circuit

In normal operation, the VLT
Input A (terminals 11, 16) is connected to an external trip circuit (such as a low-pressure alarm switch for a pumping
system). When the external circuit activates, the soft starter trips and stops the motor.
5
5
1
Control voltage (model dependent)
2
24 V DC output
3
Remote control inputs
4
Motor thermistor input (PTC only)
5
Relay outputs
6
3-phase supply
7
Motor terminals
Illustration 5.13 Auxiliary Trip Circuit
Parameter settings:
Parameter 3-3 Input A Function.
-
Parameter 3-4 Input A Name.
46
®
VLT
®
Soft Starter MCD 500 is controlled via a remote 2-wire signal (terminals 17, 18).
K1
F
6
A
S3
S1
S2
Select Input Trip (N/O) - assigns input A to auxiliary trip (N/O) function.
Danfoss A/S © 05/2016 All rights reserved.
Soft Starter MCD 500
1/L1
2/T1
3/L2
4/T2
5/L3
6/T3
E
A4
13
A5
14
1
21
A6
22
5
07
+
24
08
2
24
33
VD
11
34
16
+
15
17
3
18
25
05
4
06
S1
Start/stop contact
S2
Reset contact
S3
Auxiliary trip contact
13, 14
Relay output A
21, 22, 24
Relay output B
33, 34
Relay output C
7