Initial settings of the logging function

The following describes the initial setting procedure to use the logging function.
Setting procedure
1.
Set "A/D conversion enable/disable setting" to "A/D conversion enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]  [A/D conversion enable/disable setting]
2.
Set "Logging enable/disable setting" to "Enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter] 
[Application setting]  [Logging function]
3.
Set the target data to be logged in "Logging data setting". Set either of "Digital output value" or "Digital operation value"
for each channel.
4.
Set the cycle to store the logging data to "Logging cycle setting value".
5.
Select a unit of the logging cycle setting value in "Logging cycle unit setting".
6.
Set a condition to generate a hold trigger in "Level trigger condition setting". To use 'CH1 Logging hold request'
(Un\G471), set "Disable". To use the level trigger, set either of "Level trigger (condition: Rise)", "Level trigger (condition:
Fall)", or "Level trigger (condition: Rise and fall)".
7.
Set a number of the data points to be collected for the time period from the occurrence of a hold trigger to logging stop in
"Post-trigger logging points".
8.
Set a buffer memory address to be monitored with a level trigger to "Trigger data".
9.
Set whether to enable or disable the logging read function in "Read interrupt enable/disable setting"
10.
Set a level where a level trigger operates for "Trigger setting value".
1 FUNCTIONS
73