Mitsubishi Electric R60AD8-G User Manual page 60

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

■Operations of when 'Operating condition setting request' (Y9) is turned on and off
• During the difference conversion, even when 'Operating condition setting request' (Y9) is turned on and off, the difference
conversion continues without updating the difference conversion reference value. To updating the difference conversion
reference value, restart the difference conversion by changing CH1 Difference conversion trigger (Un\G470) from Trigger
request (1) to No request (0), and Trigger request (1) again.
• CH1 Difference conversion trigger (Un\G470) does not become valid even when the trigger changes from No request (0) to
Trigger request (1) when 'Operating condition setting request' (Y9) is turned off and on. After turning on and off 'Operating
condition setting request' (Y9), change CH1 Difference conversion trigger (Un\G470) from No request (0) to Trigger request
(1) again.
'Operating condition setting
request' (Y9)
'Operating condition setting
completed flag' (X9)
'CH1 Difference conversion
trigger' (Un\G470)
CH1 Digital operation value
before difference conversion
'CH1 Difference conversion
reference value' (Un\G432)
'CH1 Digital operation value'
(Un\G402)
'CH1 Difference conversion
status flag' (Un\G408)
1 FUNCTIONS
58
1.10 Difference Conversion Function
ON
OFF
ON
OFF
Trigger request (1)
9950
10001 10100 10010 10510 12000 12100 13250
10000
10000 10000 10000 10000 10000 10000 10000
Not updated
-50
1
100
10
510
Converting difference (1)
Trigger request (1)
No request (0)
13000
13310
Updated
13000
13000
2000 12100 13250
0
310
Not converted (0)
Converting difference (1)