■Checking the trigger generation time
The trigger generation time can be checked with 'CH1 Trigger generation time' (Un\G444 to Un\G448).
Ex.
When 'CH1 Trigger generation time' (Un\G444 to Un\G448) is monitored
'CH1 Trigger generation time (First/Last two digits of the year)' (Un\G444)
'CH1 Trigger generation time (Month/Day)' (Un\G445)
'CH1 Trigger generation time (Hour/Minute)' (Un\G446)
'CH1 Trigger generation time (Second/Day of the week)' (Un\G447)
'CH1 Trigger generation time (Millisecond)' (Un\G448)
• First two digits of the year, last two digits of the year, month, day, hour, minute, second, and millisecond are all stored in the
BCD code.
• In the day of the week segment, one of the following values in the BCD code indicating the corresponding day is stored.
Sunday: 00H, Monday: 01H, Tuesday: 02H, Wednesday: 03H, Thursday: 04H, Friday: 05H, Saturday: 06H
Resuming the logging
It may take time until ON (1) is stored in 'CH1 Logging hold flag' (Un\G409) after 'CH1 Logging hold request' (Un\G471) is
changed from off to on.
To resume logging, check that ON (1) is stored in 'CH1 Logging hold flag' (Un\G409) and 'CH1 Logging hold request'
(Un\G471) is changed from on to off. After logging resumes, the value is stored from the head buffer memory area of 'CH1
Logging data' (Un\G10000 to Un\G10999).
In addition, OFF (0) is stored in 'CH1 Logging hold flag' (Un\G409).
'CH1 Logging hold request'
OFF(0)
(Un\G471)
'CH1 Logging hold flag'
(Un\G409)
Logging status
Logging
Logging does not stop when 'CH1 Logging hold request' (Un\G471) is changed from on to off before ON (1) is stored in 'CH1
Logging hold flag' (Un\G409).
'CH1 Logging hold request'
(Un\G471)
'CH1 Logging hold flag'
(Un\G409)
Logging status
b15
Controlled by the A/D converter module
Controlled by the program
ON(1)
OFF(0)
Logging post-trigger
Logging held
data
Controlled by the A/D converter module
Controlled by the program
OFF(0)
ON(1)
OFF(0)
Logging
Logging post-trigger data
to
First two digits of the year
Month
Hour
Second
Millisecond (higher-order digits)
OFF(0)
ON(1)
OFF(0)
Logging
OFF(0)
Logging
b8 b7
to
Last two digits of the year
Day
Minute
Day of the week
Millisecond (lower-order digits)
The logging does not stop.