10.1

SIL2 Mode

This section describes the settings necessary for operating the R60AD8-G in SIL2 mode.
Creating a new project (remote head module side)
Create a new project with the remote head module, and add necessary modules.
1.
Create a project with the remote head module. Depending on the system configuration, specify the RJ72GF15-T2 or
RJ72GF15-T2 (LR).
2.
Depending on the system configuration, add "R60AD8-G(S2M)", "R60AD8-G(S2S)", "R60DA8-G", and "RY40PT5B".
Setting parameters on the remote head module side
With the created project, set the parameters.
1.
Configure "Network Required Setting" in "CPU Parameter" for the remote head module.
2.
Set the module parameters for "R60AD8-G(S2M)" and "R60DA8-G".
Page 251 Module parameters for "R60AD8-G(S2M)"
Page 251 Module parameters for "R60DA8-G"
• There is no need to set module parameters for "R60AD8-G(S2S)" because the module parameters for "R60AD8-G(S2M)"
are used automatically.
• Do not change the default module parameters for "RY40PT5B".
3.
Write the set parameters to the remote head module on the intelligent device station. Then reset the remote head
module or turn off and on the power.
4.
Save the project.
The project on the remote head module side is used for configuring the safety communication setting in a
project on the SIL2 Process CPU side. For details, refer to the following.
Page 254 Safety communication setting
10 FUNCTIONS
250
10.1 SIL2 Mode