Shift Function - Mitsubishi Electric R60AD8-G User Manual

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

1.8

Shift Function

This function adds (shifts) a set conversion value shift amount to a digital output value and stores the result in the buffer
memory area. The digital operation value reflects the change in the conversion value shift amount on a realtime basis.
Therefore, fine adjustment can be easily performed when the system starts.
Operation
A set conversion value shift amount is added to the digital operation value. The digital operation value with shift addition is
stored in 'CH1 Digital operation value' (Un\G402). The conversion value shift amount is added in every sampling cycle for
sampling processing and is added in every averaging process cycle for averaging processing. After that, the added values are
stored in 'CH1 Digital operation value' (Un\G402). If a value is set to the conversion value shift amount, the conversion value
shift amount is added regardless of turning on and off 'Operating condition setting request' (Y9).
Setting procedure
Set a value for "Conversion value shift amount".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter] 
[Application setting]  [Shift function]
Item
Conversion value shift amount
Setting example
Ex.
When the I/O characteristics is adjusted in a channel where the input range of 0 to 5V is set by the shift function
32000
31990
0
-10
Voltage input
0
5
*1 These values are also applied to the case of digital output values (32 bits).
(1) 'CH1 Digital output value' (Un\G400)
+
'CH1 Conversion value shift amount' (Un\G472) "+10"
(2)
(2) 'CH1 Digital operation value' (Un\G402)
(1)
Analog input voltage (V)
5
Digital output value
-10
31990
Setting range
-32768 to 32767
*1
Digital operation value
0
32000
1
1 FUNCTIONS
51
1.8 Shift Function