Mitsubishi Electric R60AD8-G User Manual page 179

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

CH1 Alert output setting (Rate alarm)
Set whether to enable or disable the alert output of the rate alarm.
For details on the alert output function, refer to the following.
Page 30 Alert Output Function
Setting value
0
1
If a value other than the above is set, an alert output setting (Rate alarm) range error (error code: 1B8H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
• CH Alert output setting (Rate alarm)
CH1
CH2
CH3
CH4
513
713
913
1113
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is Disable (1) for all channels.
Alert output setting [Q compatible mode]
When the Q compatible mode function is used, set whether to enable or disable the alert output of process alarms and rate
alarms.
b15 b14 b13 b12 b11 b10 b9
CH8
CH7
CH6
CH5
CH4
CH3
CH2
(2)
(1) 0: Process alarm enabled, 1: Process alarm disabled
(2) 0: Rate alarm enabled, 1: Rate alarm disabled
■Buffer memory address
The following shows the buffer memory address of this area.
Only the R60AD8-G can use this area.
Buffer memory name
Alert output setting (Process alarm)/Alert output
setting (Rate alarm)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
• b0 to b7: The default value is Process alarm disabled (1).
• b8 to b15: The default value is Rate alarm disabled (1).
CH5
CH6
CH7
CH8
1313
1513
1713
1913
b8
b7
b6
b5
b4
b3
b2
CH1
CH8
CH7
CH6
CH5
CH4
CH3
(1)
CH1
CH2
48
Setting content
Enable
Disable
CH9
CH10
CH11
2113
2313
2513
b1
b0
CH2
CH1
CH3
CH4
CH5
CH12
CH13
CH14
CH15
2713
2913
3113
3313
CH6
CH7
APPX
Appendix 3 Buffer Memory Areas
CH16
3513
A
CH8
177

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60ad16-g

Table of Contents