Mitsubishi Electric R60AD8-G User Manual page 54

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

Ex.
When the I/O characteristics is adjusted in a channel where the input range of -10 to 10V is set by the shift function
(52000)
32767
32000
0
-12000
-32000
-10
-5
Voltage input
-10
-5
0
5
10
*1 Because the value exceeds the range of -32768 to 32767, the value is fixed to 32767 (the upper limit value).
*2 These values are also applied to the case of digital output values (32 bits).
1 FUNCTIONS
52
1.8 Shift Function
(2)
(1)
0
5
Digital output value
-32000
-16000
0
16000
32000
Analog input voltage (V)
10
*2
(1) 'CH1 Digital output value' (Un\G400)
+
'CH1 Conversion value shift amount' (Un\G472)
"+20000"
(2) 'CH1 Digital operation value' (Un\G402)
Digital operation value
-12000
4000
20000
*1
32767
*1
32767

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60ad16-g

Table of Contents