Chapter 6 Specifications; Performance Specifications - Mitsubishi Electric R60AD8-G User Manual

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

6
SPECIFICATIONS
This chapter describes the performance specifications and function list of the R60AD8-G in SIL2 mode.
6.1

Performance Specifications

Performance specifications of the R60AD8-G in SIL2 mode are as follows.
Item
Number of analog input channels
Analog input voltage
Analog input current
Digital output
I/O conversion characteristics, resolution
Accuracy (Accuracy of the maximum digital output
*3
value)
Accuracy of double input discrepancy detection
Common mode characteristics
*6
Conversion speed
*7
Response time
SIL2 A/D conversion cycle setting
Control cycle time
Absolute maximum input
Isolation method
Withstand voltage
Isolation resistance
Number of occupied I/O points
External interface
Applicable wire size
When A6CON1 and A6CON4
are used
When A6CON2 is used
Connector for external devices
Internal current consumption (5VDC)
External dimensions
Height
Width
Depth
Weight
Specifications
8 channels
-10 to 10VDC (Input resistance: 1M)
0 to 20mADC (input resistance 250)
16-bit signed binary value (-32768 to 32767)
*1
Analog input range
Voltage
0 to 10V
0 to 5V
1 to 5V
1 to 5V (extended mode)
-10 to 10V
User range setting
(voltage)
Current
0 to 20mA
4 to 20mA
4 to 20mA (extended
mode)
User range setting
(current)
Reference accuracy: Within 0.1% (32 digit)
Temperature coefficient: 35ppm/ (0.0035%/)
*10
0.5 to 5.0%
Common mode voltage between input and common ground (input voltage 0V): 500VAC
Common mode voltage rejection ratio (VCM < 500V): 60Hz 107dB, 50Hz 106dB
12ms/CH
20ms
*8
700 to 32767ms
12ms
Voltage: 15V, Current: 30mA
Between I/O terminals and programmable controller power supply: Transformer
Between analog input channels: Transformer
Between I/O terminals and programmable controller power supply: 500VACrms for 1 minute
Between analog input channels: 1000VACrms for 1 minute
Between I/O terminals and programmable controller power supply: 10M or higher, at 500VDC
Between analog input channels: 10M or higher, at 500VDC
16 points, 1 slot (I/O assignment: Intelligent 16 points)
40-pin connector
0.088 to 0.3 (28 to 22 AWG) (stranded wire)
0.088 to 0.24 (28 to 24 AWG) (stranded wire)
A6CON1, A6CON2, A6CON4 (sold separately)
0.33A
106mm (Base unit mounting side: 98mm)
27.8mm
110mm
0.19kg
Digital output value
0 to 32000
-8000 to 32767
-32000 to 32000
0 to 32000
-8000 to 32767
-32000 to 32000
*4
*5
*9
6.1 Performance Specifications
Resolution
312.5V
156.3V
125.0V
125.0V
312.5V
*2
50.0V
625.0nA
500.0nA
500.0nA
*2
190.6nA
6 SPECIFICATIONS
225
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60ad16-g

Table of Contents