Mitsubishi Electric R60AD8-G User Manual page 49

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

Notification
When an input signal error is detected, an error is notified as follows.
• Input signal error (1) is stored in the corresponding bit of 'Input signal error detection flag' (Un\G49).
• 'Input signal error detection signal' (XC) turns on.
• The corresponding bit of 'A/D conversion completed flag' (Un\G10) turns off.
• The ALM LED flashes.
In addition, an alarm code is stored in 'Latest alarm code' (Un\G3750).
For details on the alarm codes, refer to the following.
Page 112 List of Alarm Codes
1 FUNCTIONS
1.7 Input Signal Error Detection Function
1