CH1 Rate alarm lower limit value
Set a lower limit value of the change rate of digital output values to detect a rate alarm.
For details on the alert output function, refer to the following.
Page 30 Alert Output Function
■Buffer memory address
The following shows the buffer memory address of this area.
• CH Rate alarm lower limit value
CH1
CH2
CH3
526
726
926
• CH Rate alarm lower limit value (in Q compatible mode)
CH1
CH2
CH3
127
129
131
■Setting range
The setting range is from -32768 to 32767 (-3276.8 to 3276.7%). (Set it in a unit of 0.1%.)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
• When using the rate alarm, configure the 2-step settings for the rate alarm upper limit value and lower limit
value.
• In the channel where a set value does not satisfy the condition "the rate alarm lower limit value  the rate
alarm upper limit value", a rate alarm upper/lower limit setting value inversion error (error code: 1BAH)
occurs.
• Since the default value is 0, change the setting value.
CH1 Input signal error detection setting
Set a condition for detecting an input signal error.
For details on the input signal error detection function, refer to the following.
Page 38 Input Signal Error Detection Function
Setting value
0
1
2
3
4
If a value other than the above is set, an input signal error detection setting range error (error code: 1C0H) occurs.
If Simple disconnection detection (4) is selected for the channel where the input range setting is other than the extended
mode, a disconnection detection enabled range setting range error (error code: 1C6H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
• CH Input signal error detection setting
CH1
CH2
CH3
528
728
928
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
APPX
182
Appendix 3 Buffer Memory Areas
CH4
CH5
CH6
CH7
1126
1326
1526
1726
CH4
CH5
CH6
CH7
133
135
137
139
CH4
CH5
CH6
CH7
1128
1328
1528
1728
CH8
CH9
CH10
CH11
1926
2126
2326
2526
CH8
CH9
CH10
CH11
141
Setting content
Disable
Upper and lower limit detection
Lower limit detection
Upper limit detection
Simple disconnection detection
CH8
CH9
CH10
CH11
1928
2128
2328
2528
CH12
CH13
CH14
CH15
2726
2926
3126
3326
CH12
CH13
CH14
CH15
CH12
CH13
CH14
CH15
2728
2928
3128
3328
CH16
3526
CH16
CH16
3528