Mitsubishi Electric R60AD8-G User Manual page 189

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

CH1 Input signal error detection upper limit set value [Q compatible mode]
In the Q compatible mode, set an upper limit value to detect an input signal error.
The operation varies depending on the value set in 'CH1 Input signal error detection extension/input signal error detection
setting' (Un\G47).
• When Upper limit value/lower limit value same (0) is set
The value set in this area is ignored.
• When Upper limit value/lower limit value different (1) is set
Set an upper limit value to detect an input signal error.
■Buffer memory address
The following shows the buffer memory address of this area.
Only the R60AD8-G can use this area.
Buffer memory name
CH Input signal error detection upper limit set
value (in Q compatible mode)
■Setting range
The setting range is from 0 to 250 (0 to 25.0%). Set it in a unit of 1 (0.1%).
In the channel where a value out of the above range is set, an input signal error detection setting value range error (error
code: 1C1H) occurs.
However, setting 251 disables the input signal error detection.
For the setting method, refer to the following.
Page 185 CH1 Input signal error detection setting value/lower limit set value [Q compatible mode]
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 50 for all channels.
CH1 Logging enable/disable setting
Set whether to enable or disable the logging function.
For details on the logging function, refer to the following.
Page 61 Logging Function
Setting value
0
1
If a value other than the above is set, a logging enable/disable setting range error (error code: 1D0H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
• CH Logging enable/disable setting
CH1
CH2
CH3
CH4
535
735
935
1135
• CH Logging enable/disable setting (in Q compatible mode)
CH1
CH2
CH3
CH4
1000
1001
1002
1003
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is Disable (1) for all channels.
CH1
CH2
150
151
CH5
CH6
CH7
CH8
1335
1535
1735
1935
CH5
CH6
CH7
CH8
1004
1005
1006
1007
CH3
CH4
CH5
152
153
154
Setting content
Enable
Disable
CH9
CH10
CH11
CH12
2135
2335
2535
2735
CH9
CH10
CH11
CH12
Appendix 3 Buffer Memory Areas
CH6
CH7
CH8
155
156
157
CH13
CH14
CH15
CH16
2935
3135
3335
3535
CH13
CH14
CH15
CH16
APPX