Precautions For Channel Number And Output Signal - Mitsubishi Electric R60AD8-G User Manual

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

Precautions for channel number and output signal

Before wiring for SIL2 mode, pay attention to the following points.
Precautions for channel number
All the channels used for the R60AD8-G (Main), R60AD8-G (Sub), and R60DA8-G for diagnostics should use the same
channel number.
Ex.
When the R60AD8-G (Main) and R60AD8-G (Sub) use CH1 to make A/D conversion, the R60DA8-G for diagnostics must use
CH1.
Precautions for output signal
When a relay is wired with the RY40PT5B, the output signals used for the RY40PT5B should be wired as follows.
Output signals used
for the RY40PT5B
R60AD8-G (Main) side
R60AD8-G (Sub) side
Ex.
When the R60AD8-G (Main) and R60AD8-G (Sub) use CH1, wire the R60AD8-G (Main) to Y0 of the RY40PT5B and wire the
R60AD8-G (Sub) to Y1 of the RY40PT5B.
9 INSTALLATION AND WIRING
248
9.2 External Wiring
Channel used by the R60AD8-G
CH1
CH2
Y0
Y2
Y1
Y3
CH3
CH4
Y4
Y6
Y5
Y7
CH5
CH6
Y8
YA
Y9
YB
CH7
CH8
YC
YE
YD
YF