10.7

Digital Clipping Function

This function fixes the digital operation value with the maximum digital output value and the minimum digital output value
when the corresponding current or voltage exceeds the input range.
List of output ranges
The following table lists the output ranges of the digital operation values when the digital clipping function is enabled with each
input range.
Input range
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
0 to 10V
-10 to 10V
User range setting
4 to 20mA (extended mode)
1 to 5V (extended mode)
When the determined digital operation value is out of the range of -32768 to 32767, the digital clipping
function is performed to the following values.
• When the digital operation value is 32767 or greater: 32767
• When the digital operation value is -32768 or smaller: -32768
Setting procedure
Set "Digital clipping enable/disable setting" to "Enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter] 
[Application setting]  [Digital clipping function]
10 FUNCTIONS
272
10.7 Digital Clipping Function
Output range of digital operation values
Digital clipping function is enabled
0 to 32000
-32000 to 32000
-8000 to 32767
Digital clipping function is disabled
-768 to 32767
-32768 to 32767
-8768 to 32767