Safety communication setting
Configure the safety communication setting using the project on the remote head module side. For details on safety
communications, refer to the MELSEC iQ-R CC-Link IE Field Network User's Manual (Application).
1.
Open a project on the SIL2 Process CPU side.
2.
Set "To Use or Not to Use the Safety Communication Setting" in "Module Parameter" for the master/local module to
"Use".
[Navigation window]  [Parameter]  [Module Information]  Target module  [Module Parameter]  [Application
setting]  [Safety Communication Setting]
3.
Double-click "Safety Communication Setting" in "Module Parameter" for the master/local module, and display the "Safety
Communication Setting" window.
4.
Select "Local Network" for "Communication Destination", and display the "Select the target module for the Safety
Communication Setting" window.
5.
Click the [Import Setting] button, and select the SIL2 system (remote head module side) project.
10 FUNCTIONS
254
10.1 SIL2 Mode