Setting example
Ex.
When 20000 is set to the scaling upper limit value and 4000 is set to the scaling lower limit value for the R60AD8-G with the
input range of 0 to 5V
Scaling upper limit value 20000
Scaling lower limit value 4000
Voltage input (V)
0
1
2
3
4
5
Ex.
When 20000 is set to the scaling upper limit value and 4000 is set to the scaling lower limit value for the R60AD8-G with the
input range of -10 to 10V
Scaling upper limit value: 20000
Scaling lower limit value: 4000
Voltage input (V)
-10
-5
0
5
10
10 FUNCTIONS
270
10.6 Scaling Function
32000
0
0
Digital operation value before scaling
0
6400
12800
19200
25600
32000
32000
0
-32000
-10
0
Digital operation value before scaling
-32000
-16000
0
16000
32000
Analog input voltage (V)
5
Digital operation value
(scaling value)
4000
7200
10400
13600
16800
20000
Analog input voltage (V)
10
Digital operation value
(scaling value)
4000
8000
12000
16000
20000