Mitsubishi Electric R60AD8-G User Manual page 195

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

CH1 Trigger data [Q compatible mode]
In the Q compatible mode, set a buffer memory address to be monitored using a level trigger.
Set the buffer memory address where the target data for monitoring is stored.
■Buffer memory address
The following shows the buffer memory address of this area.
Only the R60AD8-G can use this area.
Buffer memory name
CH1 Trigger data (in Q compatible mode)
■Setting range
The setting range is from 0 to 9999.
If a value out of the range is set, a trigger data setting range error (error code: 1D6H) occurs. Logging cannot be performed.
When 'CH1 Logging enable/disable setting' (Un\G1000) is set to Disable (1), the setting for 'CH1 Trigger data' (Un\G1064) is
ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default values are set as shown below.
Channel
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH1 Trigger setting value
Set a level to generate a level trigger.
For details on the logging function, refer to the following.
Page 61 Logging Function
■Buffer memory address
The following shows the buffer memory address of this area.
• CH Trigger setting value
CH1
CH2
CH3
CH4
542
742
942
1142
• CH Trigger setting value (in Q compatible mode)
CH1
CH2
CH3
CH4
1082
1083
1084
1085
■Setting range
The setting range is from -32768 to 32767.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
CH1
CH2
1064
1065
Default value
54
55
56
57
58
59
60
61
CH5
CH6
CH7
CH8
1342
1542
1742
1942
CH5
CH6
CH7
CH8
1086
1087
1088
1089
CH3
CH4
CH5
1066
1067
1068
Buffer memory area to be monitored
CH1 Digital operation value (Un\G54)
CH2 Digital operation value (Un\G55)
CH3 Digital operation value (Un\G56)
CH4 Digital operation value (Un\G57)
CH5 Digital operation value (Un\G58)
CH6 Digital operation value (Un\G59)
CH7 Digital operation value (Un\G60)
CH8 Digital operation value (Un\G61)
CH9
CH10
CH11
CH12
2142
2342
2542
2742
CH9
CH10
CH11
CH12
Appendix 3 Buffer Memory Areas
CH6
CH7
CH8
1069
1070
1071
CH13
CH14
CH15
CH16
2942
3142
3342
3542
CH13
CH14
CH15
CH16
APPX
A
193

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60ad16-g