A/D Conversion Enable/Disable Setting Function; A/D Conversion Method - Mitsubishi Electric R60AD8-G User Manual

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

10.4

A/D Conversion Enable/Disable Setting Function

This function controls whether to enable or disable the A/D conversion for each channel. Disabling the A/D conversion for
unused channels reduces the conversion cycles.
Setting procedure
Set "A/D conversion enable/disable setting" to "A/D conversion enable" or "A/D conversion disable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]  [A/D conversion enable/disable setting function]
10.5

A/D Conversion Method

An A/D conversion method can be set for each channel.
Sampling processing
This function converts analog input values to digital operation values at every sampling period.
The sampling period is "Conversion speed (12ms)  Number of conversion enabled channels".
Whether to enable or disable the A/D conversion can be set for each channel. Disabling the A/D conversion
for unused channels reduces the conversion cycles.
Conversion cycle that applies when CH1 to CH3 is set to A/D conversion enabled
• 12  3 = 36 (ms)
The conversion cycle is 36 (ms).
Analog input values are converted to digital operation values of CH1 to CH3 every 36ms.
10 FUNCTIONS
266
10.4 A/D Conversion Enable/Disable Setting Function

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60ad16-g

Table of Contents