A/D conversion enable/disable setting [Q compatible mode]
When the Q compatible mode function is used, set whether to enable or disable the A/D conversion.
b15 b14 b13 b12 b11 b10 b9
CH8
CH7
CH6
CH5
CH4
(2)
(1) 0: A/D conversion enabled, 1: A/D conversion disabled
(2) b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Only the R60AD8-G can use this area.
Buffer memory name
A/D conversion enable/disable setting (in Q
compatible mode)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is A/D conversion disabled (1).
CH1 Averaging process specification
Select processing to be performed among the sampling processing, averaging processing, and filter processing.
Averaging processing consists of time average, count average, and moving average.
Setting value
0
1
2
3
4
If a value other than the above is set, an averaging process specification setting range error (error code: 191H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
• CH Averaging process specification
CH1
CH2
CH3
501
701
901
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is Sampling processing (0) for all channels.
APPX
170
Appendix 3 Buffer Memory Areas
b8
b7
b6
b5
b4
CH3
CH2
CH1
CH8
CH7
CH6
CH5
CH1
0
CH4
CH5
CH6
1101
1301
1501
b3
b2
b1
b0
CH4
CH3
CH2
CH1
(1)
CH2
CH3
CH4
Setting content
Sampling processing
Time average
Count average
Moving average
Primary delay filter
CH7
CH8
CH9
CH10
1701
1901
2101
2301
CH5
CH6
CH11
CH12
CH13
CH14
2501
2701
2901
3101
CH7
CH8
CH15
CH16
3301
3501