Mitsubishi Electric R60AD8-G User Manual page 275

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

Setting example
Ex.
When the following values are used for the R60AD8-G with the input range of 0 to 5V
• "Scaling enable/disable setting": "Enable"
• "Scaling upper limit value": 12000
• "Scaling lower limit value": 2000
• "Digitalclip enable/disable setting": "Enable"
32767
32000
12000
2000
0
-768
0
Input voltage (V)
-0.12
0
1
2
3
4
5
5.096
When the digital clipping function is used with the scaling function, scale conversion is performed on the value
obtained after digital clipping.
(1)
(2)
(3)
Analog input voltage (V)
5
Digital operation value before processing Digital operation value to be output
-768
0
6400
12800
19200
25600
32000
32767
(1) Digital operation value before processing
Digital clipping
-768 to 32767
0 to 32000
(2) Value after digital clipping
Scaling
0 to 32000
2000 to 12000
(3) Digital operation value to be output
2000
2000
4000
6000
8000
10000
12000
12000
10 FUNCTIONS
10.7 Digital Clipping Function
10
273

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60ad16-g

Table of Contents