10.9
Self-diagnostic Function
This function periodically monitors the operating status of the R60AD8-G, such as the MPU (operation processing unit)
operating status, power supply voltage status (overvoltage and undervoltage), safety communications status, and built-in
programs operating status, for any errors.
If an error is detected by the self-diagnostic function, digital operation values of all channels become the OFF value
(equivalent to 0V/0mA) and safety communications are stopped in the safety layer. If hardware failure (error code: 3001H) is
detected by the self-diagnostic function in the R60AD8-G (Main), a safety mutual monitoring error (error code: 3020H) occurs
in the R60AD8-G (Sub). If hardware failure is detected in the R60AD8-G (Sub), a safety mutual monitoring error (error code:
3020H) occurs in the R60AD8-G (Main).
List of self-diagnostic functions
Diagnostics
Diagnostics
name
H/W diagnostic
Verifies whether the MPU (operation
function
processing unit) in the R60AD8-G operates
normally.
Power supply
Monitors the power supply voltage in the
diagnostic function
R60AD8-G, and when it detects an error,
stops the MPU operation and shuts down
the system.
Safety layer
Monitors the status of safety
diagnostic function
communications between the R60AD8-G
(Main) and SIL2 Process CPU.
F/W operation
Monitors program operating status in the
monitoring function
R60AD8-G.
*1 indicates that the function is applicable, and indicates that the function is not applicable.
*2 The diagnostic function is executed immediately after power-on. For SIL2 analog input systems, it starts after start-up diagnostics is
complete. Due to the time needed for diagnostic functions, SIL2 analog input systems take more time to start up than normal systems.
*3 The diagnostic function is executed periodically after the SIL2 analog input system starts operating normally.
*4 An error code to be generated varies depending on the detection.
If an error is detected in the send/receive data of the module, hardware failure (error code 3001H) is generated.
If an error is detected in data link, no error code is generated. The error is logged in the event history.
*5 The power is not supplied to circuits such as microcomputers and the system is in the safety state.
The module is in the following state at system shutdown.
On the GX Works3 system monitor, it is indicated that the module is not mounted.
The RUN LED, ERR LED, ALM LED, and S MODE LED of the module turn off.
10 FUNCTIONS
290
10.9 Self-diagnostic Function
*5
*1
Diagnostic timing
*2
At start-up
During
operation
Error to be
generated after
error detection
*3
Hardware failure (error
code: 3001H)
Hardware failure (error
code: 3001H)
*4
Hardware failure (error
code: 3001H)
Diagnostic
cycle
8 hours or less
8 hours or less
Every 12ms
Every 12ms