2.4

Refresh Setting

Setting procedure
Set the buffer memory area of the A/D converter module to be refreshed.
This refresh setting eliminates the need for reading/writing data by programming.
1.
Start Module parameter.
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Refresh
settings]
2.
Click "Target", and set the auto refresh destination.
• When "Refresh Destination" is "Module Label"
Set whether to enable or disable the refresh by setting "Level data 0" to Valid or Invalid.
• When "Refresh Destination" is "Refresh Data Register (RD)"
The transfer destinations of all items are automatically set by setting the start device to "Top Device Name".
• When "Refresh Destination" is "Specified Device"
Double-click the item to be set to enter the refresh destination device.
3.
Click "Refresh Group" to set the timing to refresh.
Set "Refresh Group" to "At the Execution Time of END Instruction" or "At the Execution Time of Specified Program".
When "At the Execution Time of Specified Program" is set, double-click "Group [n] (n: 1-64)" and set a value of 1 to 64.
When the refresh is enabled, the values of the refresh destination are enabled at the refresh timing set with
the engineering tool. At this time, the buffer memory areas are overwritten with the values of the refresh
destination. To change the value in the refresh target buffer memory area, create a program to change the
module label of the refresh destination and the device value.