Mitsubishi Electric R60AD8-G User Manual page 43

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

Clearing input signal errors
One of the following methods for clearing input signal errors can be selected by setting Input signal error detection auto-clear
enable/disable setting (Un\G302).
■When Input signal error detection auto-clear enable/disable setting is set to Enable (0)
After the analog input value returns within the setting range, the A/D converter module arranges the following status
automatically. After the analog input value returns within the setting range, turning on and off 'Error clear request' (YF) is not
required.
• 'Input signal error detection flag' (Un\G40) is cleared.
• 'Input signal error detection signal' (XC) turns off.
• The ALM LED turns off.
'Latest alarm code' (Un\G2) is not cleared.
After the analog input value returns within the setting range, turn on and off 'Error clear request' (YF) to clear
'Latest alarm code' (Un\G2).
1 FUNCTIONS
1.7 Input Signal Error Detection Function
1
41