CH1 Input signal error detection lower limit set value
Set a lower limit value to detect an error for the input analog value.
For details on the input signal error detection function, refer to the following.
Page 38 Input Signal Error Detection Function
■Buffer memory address
The following shows the buffer memory address of this area.
• CH Input signal error detection lower limit set value
CH1
CH2
CH3
529
729
929
■Setting range
The setting range is from 0 to 250 (0 to 25.0%). Set it in a unit of 1 (0.1%).
For example, set 150 in the buffer memory area to set 15%.
In the channel where a value out of the range is set, an input signal error detection setting value range error (error code:
1C1H) occurs.
The input signal error detection lower limit value is calculated by using the input signal error detection lower limit set value as
follows. The input signal error detection lower limit value to be calculated varies depending on the input range used.
Input signal error detection lower limit value = Lower limit value of each range - (Gain value of each range - Offset value of
each range)  (Input signal error detection lower limit set value/1000)
Ex.
When 'CH1 Input signal error detection lower limit set value' (Un\G529) is set to 100 (10%)
Range used: 4 to 20mA
The input signal error detection lower limit value is calculated as follows:
Input signal error detection lower limit value = 4 - (20 - 4) ×
Detection conditions vary depending on the setting of 'CH1 Input signal error detection setting' (Un\G528) as follows:
• When 'CH1 Input signal error detection setting' (Un\G528) is set to Upper and lower limit detection (1), the detection is
performed with both the input signal error detection upper limit value and the input signal error detection lower limit value.
• When 'CH1 Input signal error detection setting' (Un\G528) is set to Lower limit detection (2), the detection is performed only
with the input signal error detection lower limit value.
• When 'CH1 Input signal error detection setting' (Un\G528) is set to Upper limit detection (3), the value set in this area is
ignored.
• When 'CH1 Input signal error detection setting' (Un\G528) is set to Simple disconnection detection (4), the value set in this
area is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 50 for all channels.
APPX
184
Appendix 3 Buffer Memory Areas
CH4
CH5
CH6
CH7
1129
1329
1529
1729
CH8
CH9
CH10
CH11
1929
2129
2329
2529
100
= 2.4mA
1000
CH12
CH13
CH14
CH15
2729
2929
3129
3329
CH16
3529

Hide quick links: