INSTALLATION AND WIRING
This chapter describes wiring for the R60AD8-G.
9.1

Wiring Precautions

• Check the signal layout before wiring the R60AD8-G, and connect the cables correctly. For details on the signal layout, refer
to the following.
Page 241 Connector for external devices
• Use a single-point ground for the shield of shield wires and shielded cables.

Connector for external devices

Precautions
Tighten connector screws within the specified torque range.
Screw
Connector screw (M2.6)
• Use copper wire with a temperature rating of 75 or higher for the connector.
• Use UL listed connectors if necessary for UL compliance.
Applicable connectors
Connectors for external devices used for the R60AD8-G should be ordered by the customers.
The type of applicable connectors and a reference product of crimping tool are as follows.
■40-pin connector
Type
Soldering type connector (straight type)
Crimping type connector (straight type)
Soldering type connector (dual purpose (straight/oblique) type)
*1 For application with 40 wires, use a wire with its sheath outside diameter at 1.3mm or less.
Select an adequate wire for your current value.
A6CON3 (IDC type connector (straight type)) cannot be used.
■40-pin connector crimping tool
Type
Crimping tool
For how to wire the connectors or use the crimping tool, contact FUJITSU COMPONENT LIMITED.
Connector wiring, installation procedure, disconnection procedure
For connector wiring, installation procedure, and disconnection procedure, refer to the following.
 MELSEC iQ-R Module Configuration Manual
Tightening torque range
0.20 to 0.29Nm
Model
*1
A6CON1
A6CON2
*1
A6CON4
Model
FCN-363T-T005/H
Applicable wire size
0.088 to 0.3 (28 to 22 AWG) (stranded wire)
0.088 to 0.24 (28 to 24 AWG) (stranded wire)
0.088 to 0.3 (28 to 22 AWG) (stranded wire)