Mitsubishi Electric R60AD8-G User Manual page 191

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

CH1 Logging cycle setting value
Set a cycle for storing the logging data.
For details on the logging function, refer to the following.
Page 61 Logging Function
■Buffer memory address
The following shows the buffer memory address of this area.
• CH Logging cycle setting value
CH1
CH2
CH3
CH4
537
737
937
1137
• CH Logging cycle setting value (in Q compatible mode)
CH1
CH2
CH3
CH4
1032
1033
1034
1035
■Setting range
The setting range varies depending on the setting in 'CH1 Logging cycle unit setting' (Un\G538).
CH1 Logging cycle unit setting (Un\G538)
ms (1)
s (2)
• If a value out of the range is set, a logging cycle setting value range error (error code: 1D1H) occurs. Logging cannot be
performed.
• If the set logging cycle is below the update cycle of data to be logged, a logging cycle setting disable error (error code:
1D2H) occurs. Logging cannot be performed.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 160 for all channels.
CH5
CH6
CH7
CH8
1337
1537
1737
1937
CH5
CH6
CH7
CH8
1036
1037
1038
1039
CH9
CH10
CH11
CH12
2137
2337
2537
2737
CH9
CH10
CH11
CH12
Setting range
10 to 32767
1 to 3600
Appendix 3 Buffer Memory Areas
CH13
CH14
CH15
CH16
2937
3137
3337
3537
CH13
CH14
CH15
CH16
APPX
A
189