Setting procedure
■Sampling processing
Set "Averaging process specification" to "Sampling processing".
[Navigation window] [Parameter] [Module Information] Module name [Module Parameter] [Basic setting]
[A/D conversion method]
■Averaging processing and primary delay filter
1.
Set "Averaging process specification" to "Time average", "Count average", "Moving average", or "Primary delay filter".
[Navigation window] [Parameter] [Module Information] Module model name [Module Parameter] [Basic
setting] [A/D conversion method]
2.
Set a value for "Time average/Count average/Moving average/Primary delay filter constant setting".
Item
Time average
Count average
Moving average
Primary delay filter
*1 Set a value greater than the value calculated by the following formula as the time average.
Conversion speed Number of conversion enabled channels Minimum processing times (4 times)
Setting range
*1
40 to 5000 (ms)
4 to 500 (times)
2 to 200 (times)
1 to 500 (times)
1 FUNCTIONS
1.4 A/D Conversion Method
1
25