Mitsubishi Electric R60AD8-G User Manual page 27

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

Setting procedure
■Sampling processing
Set "Averaging process specification" to "Sampling processing".
[Navigation window]  [Parameter]  [Module Information]  Module name  [Module Parameter]  [Basic setting] 
[A/D conversion method]
■Averaging processing and primary delay filter
1.
Set "Averaging process specification" to "Time average", "Count average", "Moving average", or "Primary delay filter".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]  [A/D conversion method]
2.
Set a value for "Time average/Count average/Moving average/Primary delay filter constant setting".
Item
Time average
Count average
Moving average
Primary delay filter
*1 Set a value greater than the value calculated by the following formula as the time average.
Conversion speed  Number of conversion enabled channels  Minimum processing times (4 times)
Setting range
*1
40 to 5000 (ms)
4 to 500 (times)
2 to 200 (times)
1 to 500 (times)