Mitsubishi Electric R60AD8-G User Manual page 120

Melsec iq-r series channel isolated analog-digital converter module
Table of Contents

Advertisement

Operating condition setting completed flag
■Device number
The following shows the device number of this input signal.
Signal name
Operating condition setting completed flag
When changing values of the buffer memory, use Operating condition setting completed flag (X9) as an interlock condition to
turn on and off 'Operating condition setting request' (Y9). For the buffer memory addresses which require turning on and off of
'Operating condition setting request' (Y9) to enable the changed values, refer to the following.
Page 125 List of buffer memory addresses
When 'Operating condition setting completed flag' (X9) is off, the A/D conversion is not performed.
When 'Operating condition setting request' (Y9) is on, 'Operating condition setting completed flag' (X9) turns off.
'Module READY' (X0)
'Operating condition setting
completed flag' (X9)
'Operating condition setting
request' (Y9)
'A/D conversion completed
flag' (XE)
APPX
118
Appendix 2 I/O Signals
CH1 to CH16
X9
Controlled by the A/D converter module
Controlled by the program
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON