Protections

Principle of
The protection functions are available with all models and versions of Ekip Touch.
Operation
Each protection is combined with a different signal (currents, voltages, frequencies, powers, etc.)
but the operating principle is common:
With the Ekip CI module, Ekip M Touch allows selecting a different TRIP configuration so that, if
TRIP
tripped, a contact of the Ekip CI module connected to an external contactor (Normal mode) is
triggered.
For more details see the Ekip M Touch parameters (page 66)
Many protection thresholds are shown on the display in two different sizes: the absolute and
References
relative values.
The relative value depends on the type of measurement:
Protection type
Power
Voltage
Frequency
Rating
Protection
The protections listed in the following chapters are grouped by packages, whose availability
packages
depends on the Trip unit model and version and possible installation as an additional package:
Package
Standard Protections
Voltage Protections
Advanced Voltage Protections
Frequency Protections
Power Protections
Adaptive Protections
Motor Protections
1SDH002031A1002
ECN000092998
1. If the measured signal exceeds the threshold set, the specific protection activates (pre-
alarm and/or alarm condition).
2. The alarm is shown on the display, and, based on the protection parameters set, after a
time interval (timing) it can be converted into an opening command (TRIP) to the CB's
internal Trip coil.
NOTES:
If the measured signal falls below the threshold set before the tripping time has
elapsed, Ekip Touch exits the alarm and/or timing state and returns to normal
operating condition
All the protections have a default configuration: check the parameters and change
them as needed for installation before startup
NOTE: for I and G protections, the TRIP is always managed with a Trip Coil command
Reference
In
Un
fn
Sn
Rev. B
Description
Rated size of the Trip unit
Line-to-line voltage set
Frequency set
√3 x In x Un
Page
35
46
50
54
57
65
66
SACE Tmax XT2 – XT4 | 34