Changing Settings Using Bop-2 - Siemens SINAMICS G120 Original Instructions Manual

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Appendix
A.4 Handling the BOP 2 operator panel
A.4.1

Changing settings using BOP-2

Changing settings using BOP-2
You can modify the settings of your converter by changing the values of the its parameters.
The converter only permits changes to "write" parameters. Write parameters begin with a
"P", e.g. P45.
The value of a read-only parameter cannot be changed. Read-only parameters begin with an
"r", for example: r2.
Procedure
To change write parameters using the BOP-2, proceed as follows:
1. Select the menu to display and change parameters.
Press the OK key.
2. Select the parameter filter using the arrow keys.
Press the OK key.
– STANDARD: The inverter only displays the most important parameters.
– EXPERT: The inverter displays all of the parameters.
3. Select the required number of a write parameter using the arrow keys.
Press the OK key.
4. Select the value of the write parameter using the arrow keys.
Accept the value with the OK key.
You have now changed a write parameter using the BOP-2.
The converter saves all the changes made using the BOP-2 so that they are protected
against power failure.