Write request: Changing the automatic restart mode (p1210)
Parameter p1210 defines the automatic restart mode:
● PKE, bit 12 ... 15 (AK): = 7 (change parameter value (field, word))
● PKE, bit 0 ... 10 (PNU): = 4BA hex (1210 = 4BA hex, no offset, as 1210 < 1999)
● IND, bit 8 ... 15 (page index): = 0 hex (offset 0 corresponds to 0 hex)
● IND, bit 0 ... 7 (subindex): = 0 hex (parameter is not indexed)
● PWE1, bit 0 ... 15: = 0 hex
● PWE2, bit 0 ... 15: = 1A hex (26 = 1A hex)
Figure 7-12
Telegram, to activate the automatic restart with p1210 = 26
Write request: Assign digital input 2 with the function ON/OFF1 (p0840[1] = 722.2)
In order to link digital input 2 with ON/OFF1, you must assign parameter p0840[1] (source,
ON/OFF1) the value 722.2 (DI 2). To do this, you must fill the telegram of the parameter
channel as follows:
● PKE, bit 12 ... 15 (AK): = 7 hex (change, parameter value (field, word))
● PKE, bit 0 ... 10 (PNU): = 348 hex (840 = 348 hex, no offset, as 840 < 1999)
● IND, bit 8 ... 15 (page index): = 0 hex (offset 0 ≙ 0 hex)
● IND bit 0 ... 7 (subindex): = 1 hex (command data set, CDS1 = index1)
● PWE1, bit 0 ... 15: = 2D2 hex (722 = 2D2 hex)
● PWE2, bit 10 ... 15: = 3f hex (drive object - for SINAMICS G120, always 63 = 3f hex)
● PWE2, bit 0 ... 9: = 2 hex (index or bit number of the parameter: DI 2 = r0722.2)
Figure 7-13
Telegram, to assign DI 2 with ON/OFF1
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Configuring the fieldbus
7.6 Communication via RS485
157