Procedure
To enter the data for basic commissioning, proceed as follows:
1.
2.
3.
4.
5.
6. Transfer the data from the motor rating plate to the inverter:
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Press the ESC key.
Press one of the arrow keys until the BOP-2 displays the "SETUP" menu.
4.1. Switch over the display using an arrow key: nO → YES
4.2. Press the OK key.
6.1.
6.2.
6.3.
6.4.
6.5.
In the "SETUP" menu, press the OK key to start basic
commissioning.
If you wish to restore all of the parameters to the factory
setting before the basic commissioning:
Select the motor control mode. The most important control
modes are:
VF LIN
V/f control with a linear characteristic for basic
applications, e.g. horizontal conveyors.
VF QUAD
V/f control with a square-law characteristic for
basic pump and fan applications.
SPD N EN
We recommend that you use the closed-loop
speed control.
Further information on the control types can be found in
Section Motor control (Page 250).
Motor standard
KW 50HZ IEC
HP 60HZ NEMA
KW 60HZ IEC 60 Hz
Rated voltage
Rated current
IEC power (kW)
NEMA (HP)
Rated speed
Commissioning
5.4 Basic commissioning
81