12.2.6

PM330 technical data

Permissible inverter overload
The inverters have different load capabilities, "High Overload" and "Low Overload",
depending on the expected.
Figure 12-6
12.2.6.1

PM330 general data

Table 12- 42 General technical data
Electrical data
Line system configurations
Line requirement
Line voltage
Line frequency
Output frequency
Displacement factor cos φ
power factor λ
Inverter efficiency
Short-circuit current rating
per IEC, in conjunction with
the specified fuses
Short-circuit current rating
per UL508C (up to
480 VAC), in conjunction
with the specified fuses
Overvoltage category
Mechanical data
Degree of protection
Protection class
Cooling method
Sound pressure level L
PA
(1 ma)
Touch protection
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Load cycles, Low Overload" and "High Overload"
Grounded TN/TT systems and non-grounded IT systems
A line reactor (2% u
) must be connected in series
k
380 V (-10%) ... 480 V (+10%)
47 ... 63 Hz
0 ... 100 Hz
0.96
0.75 ... 0.93 (with line reactor u
> 98%
110 ... 200 kW: 100 kA
110 ... 200 kW: 100 kA
Can be used on supply systems that cannot supply more than 100 kA symmetrically for a
maximum voltage of 480 VAC when they are protected with the listed fuses of type Class J
or approved semi-conductor fuses specified in the "Technical Data" section of this manual.
III according to EN 61800-5-1
IP20
according to EN 61800-5-1: Class I (with protective conductor system) and Class III (PELV)
Forced air cooling AF according to EN 60146
≤ 71 dB(A)
according to EN 61800-5-1: For the intended purpose
12.2 Technical data, Power Modules
= 2%)
k
Technical data
407