Changing the function of a digital input - Example
You want to acknowledge inverter fault messages using
digital input DI 1. To do this, you must interconnect DI1 with
the command to acknowledge faults (p2103). See the
adjacent diagram.
Procedure
To interconnect fault acknowledgment with digital input DI 1, proceed as follows:
You have interconnected digital input DI 1 with the command to acknowledge faults.
Advanced settings
You can debounce the digital input signal using parameter p0724.
For more information, please see the parameter list and the function block diagrams 2220 f
of the List Manual.
Analog inputs as digital inputs
When required, you can use analog inputs as
additional digital inputs.
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
1. Go online.
2. Select "Inputs/outputs".
3. Change the input function via the corresponding screen form.
1. Go into the menu "PARAMS".
2. As a parameter filter, select "EXPERT".
3. Set p2103 = 722.1
Adapting the terminal strip
6.2 Digital inputs
95