Siemens SINAMICS G120 Original Instructions Manual page 360

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Alarms, faults and system messages
11.3 Alarms
Figure 11-3
Emptying the alarm buffer: Alarm history
The alarm history traces up to 56 alarms.
The alarm history only takes alarms that have been removed from the alarm buffer. If the
alarm buffer is completely filled - and an additional alarm occurs - then the converter shifts all
alarms that have been removed from the alarm buffer into the alarm history. In the alarm
history, alarms are also sorted according to the "alarm time received", however, when
compared to the alarm buffer, in the inverse sequence:
● The youngest alarm is in index 8
● The second youngest alarm is in index 9
● etc.
Figure 11-4
Any alarms that have not been removed remain in the alarm buffer. The converter sorts the
alarms and closes gaps between the alarms.
360
Complete alarm buffer
Shifting alarms that have been removed into the alarm history
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120dCu230p-2

Table of Contents