Changing the function of a digital output - Example
You want to output inverter fault messages using digital
output DO 1. To do this, you must interconnect DO1 with the
alarm messages.
Procedure
Proceed as follows to interconnect digital output DO 1 with the alarm message:
You have interconnected digital output DO 1 with the alarm message.
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, please see the parameter list and the function block diagrams 2230 f
of the List Manual.
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
1. Go online.
2. Select "Inputs/outputs".
3. Change the output function via the corresponding screen form.
1. Go into the menu "PARAMS".
2. As a parameter filter, select "EXPERT".
3. Set p0731 = 52.3
Adapting the terminal strip
6.3 Digital outputs