Changing Settings - Siemens SINAMICS G120D Original Instructions Manual

Cu250d-2 series
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Parameters Description
p0010
p9761
p9762
p9763
p0970
8.9.3.4

Changing settings

Procedure
To start commissioning the safety functions, proceed as follows:
1. Go online with STARTER
2. In STARTER, select the fail-safe functions.
3. Select "Change settings".
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Drive, commissioning parameter filter
0
Ready
30
Parameter reset
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 ... FFFF FFFF.
New password
Password confirmation
Confirming the new Safety Integrated password.
Reset drive parameters
5
Starts a safety parameter reset.
After the reset, the inverter sets p0970 = 0.
Parameter
Description
p0010 = 95
Drive commissioning parameter filter
Safety Integrated commissioning
p9761
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 ... FFFF FFFF.
p9762
New password
p9763
Confirm password
8.9 Safe Torque Off (STO) safety function
Setting functions
241