Adapting the terminal strip

6.3 Digital outputs

6.3
Digital outputs
Changing the function of a digital output
Interconnect the digital output with a binector output of
your choice.
Binector outputs are marked with "BO" in the parameter
list of the List Manual.
The adjacent figure shows the terminals of the digital
outputs.
Table 6- 2
0
r0052.0
r0052.1
r0052.2
r0052.3
r0052.4
r0052.5
r0052.6
r0052.7
r0052.8
The complete list of binector outputs is provided in the List Manual.
96
Binector outputs (BO) of the inverter (selection)
Deactivating digital output
Drive ready
Drive ready for operation
Drive running
Drive fault active
OFF2 active
OFF3 active
Closing lockout active
Drive alarm active
Setpoint/actual value discrepancy
r0052.9
Process data control
r0052.10
f_actual >= p1082 (f_max)
r0052.11
Alarm: Motor current/torque limit
r0052.12
Brake active
r0052.13
Motor overload
r0052.14
Motor CW rotation
r0052.15
Inverter overload
r0053.0
DC braking active
r0053.2
f_actual > p1080 (f_min)
r0053.6
f_actual ≥ setpoint (f_setpoint)
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG