Advertisement

Commissioning
5.2 Preparing for commissioning
5.2.2

Does the motor match the converter?

The converter is preset on a motor at the factory as shown in the figure below.
Figure 5-1
The rated current of the motor must be in the range 13% to 100% of the rated converter
current.
Example: With a converter with the rated current 10.2 A, you may operate induction motors
whose rated currents are in the range 1.3 A to 10.2 A.
76
Motor data factory settings
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG