Setting functions
8.7 Application-specific functions
Commissioning the automatic restart
Procedure
Proceed as follows to commission the automatic restart:
1. If it is possible that the motor is still rotating for a longer period of time after a power
failure or after a fault, then in addition, you must activate the "flying restart" function, see
Flying restart – switching on while the motor is running (Page 284).
2. Using p1210, select the automatic restart mode that best suits your application.
Figure 8-25
Selecting the automatic restart mode
3. Set the parameters of the automatic restart function.
The method of operation of the parameters is explained in the following diagram and in
the table.