SIMOVERT P 6SE21 Series Inverters

5.3 Parameterisation

5.3.1 Changing Parameter Settings

Various digital parameters can be adjusted to match the inverter to a particular motor/installation. The procedure for
adjustment is described below:
Remove the small cover directly below the LED viewing window by inserting a small blade screwdriver into the slot
provided and levering the cover upwards. This will reveal the parameterisation push–buttons:
P
Parameter push–button
Raise
Lower
Carry out parameterisation with mains power applied to the inverter. Some parameters can be adjusted while the drive
is running (see 5.3.2) . If adjustment of a parameter is not permitted, the display will flash when the buttons are pressed.
The parameter number mode is obtained by pressing the parameter (P) push–button once. This results in the display
showing P00. The desired parameter can then be selected using the raise and lower push–buttons.
When the parameter push–button is pressed again, the contents of the selected parameter memory is displayed. The
value can then be adjusted using the raise and lower push–buttons. When the desired value has been selected,
pushing the parameter button again loads the new value into non–volatile memory and the display once again shows
the parameter number.
When all the required parameter settings have been loaded in, return to normal operating mode by selecting P00 and
then pressing P. The display will then revert to its normal frequency/output current or fault code indication.
Note
If necessary, all parameters can be reset to the factory default settings. The procedure for this is as follows:
(1)
Press P (P00 displayed).
(2)
Press
until P41 is displayed.
(3)
Press P to view the contents of P41 (000 for Europe, 001 for North America).
(4)
Press
to change 000 to 001 (Europe), or
(5)
Press P to load the new setting into memory.
(6)
Press P again.
(7)
Press
to change 001 back to 000 (Europe), or
(8)
Press P.
(9)
Press
until P00 is displayed.
(10)
Press P to return to the normal display.