A.3 Using the operator panel BOP-2
A.3.2

Changing settings using BOP-2

Changing settings using BOP-2
You can modify the settings of your inverter by changing the values of the its parameters.
The inverter only permits changes to "write" parameters. Write parameters begin with a "P",
e.g. P45.
The value of a read-only parameter cannot be changed. Read-only parameters begin with an
"r", for example: r2.
Procedure
To change write parameters using the BOP-2, proceed as follows:
1. Select the menu to display and change
parameters.
Press the OK key.
2. Select the parameter filter using the
arrow keys.
Press the OK key.
– STANDARD: The inverter only
– EXPERT: The inverter displays all
3. Select the required number of a write parameter using the arrow keys.
4. Select the value of the write parameter using the arrow keys.
You have now changed a write parameter using the BOP-2.
The inverter saves all the changes made using the BOP-2 so that they are protected against
power failure.
392
displays the most important
parameters.
of the parameters.
Press the OK key.
Accept the value with the OK key.
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC