Siemens SINAMICS G120 Original Instructions Manual page 330

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Backing up data and series commissioning
9.1 Backing up and transferring settings using a memory card
Procedure
To safely remove the memory card, proceed as follows:
You have now safely removed the memory card from the inverter.
330
1. In the Drive Navigatorselect the following screen form:
2. Click on the button to safely remove the memory card.
3. Remove the memory card from the inverter after the appropriate message has
been output.
1. Go to parameter p9400. If a memory card is correctly
inserted, then p9400 = 1.
2. Set p9400 = 2 The BOP-2 displays "BUSY" for several
seconds and then jumps to either p9400 = 3 or p9400 = 100.
3. Bei p9400 = 3 remove the memory card from the inverter.
4. When p9400 = 100 you must not remove the memory card.
In this case, set p9400 = 2 again.
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120dCu230p-2

Table of Contents