Siemens SINAMICS G120 Original Instructions Manual page 84

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning
5.4 Basic commissioning
Preconditions
● In the basic commissioning, you have selected the motor identification (MOT ID). In this
case, after the basic commissioning has been completed, the inverter issues the alarm
A07991.
● The motor is cooled down to the ambient temperature.
If the motor is too hot, the motor data identification will provide incorrect values and the
closed-loop speed control can become unstable.
Procedure
To initiate motor data identification and optimization of the motor control, proceed as follows:
1.
2.
3.
4.
5.
6.
7.
8.
You have now completed motor data identification and the closed-loop speed control has
been optimized.
84
You can recognize an active alarm from the corresponding symbol on the
BOP-2.
Press the HAND/AUTO key. The BOP-2 displays the HAND
symbol.
Switch on the motor.
Wait until the inverter switches off the motor after completion of the
motor data identification. The measurement takes several seconds.
Save the measurements so that they are protected against power
failure.
If you have also selected a rotating measurement in addition to the
motor data identification, then the inverter again issues the alarm
A07991.
Switch the motor on again in order to optimize the speed control.
Wait until the inverter switches off the motor after completion of the
optimization. The optimization can take up to one minute.
Switch the inverter control from HAND to AUTO.
Save the measurements so that they are protected against power
failure.
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG