Configuring the fieldbus
7.4 PROFIenergy profile for PROFINET
● Get_Measurement_List_with_object_number
This command returns the measured value IDs and the associated object number that
can be accessed using the "Get_Measurement_Values_with_object_number" command.
● Get_Measurement_ Values
The command returns the requested measured value using the measured value ID
● Get_Measurement_Values_with_object_number
The command returns the requested measured values using the measured value ID and
the object number. The object number corresponds to the drive object ID.
Displaying
● r5600:
● r5613:
● A08800:
General settings for PROFIenergy
● Minimum pause time: p5602
The inverter enters energy-saving mode only when the pause time sent with the
"Start_Pause" command is greater than or equal to the value for p5602.1. If the pause
time is less than p5602.1, the inverter ignores the command.
● Maximum pause time: p5606
Block PROFIenergy control commands
If you set p5611.0 = 1, you block the response of the inverter to PROFIenergy control
commands. In this case, the inverter ignores the PROFIenergy control commands.
Transition to the energy-saving mode from the PROFIdrive operating state (S4)
If you set p5611.2 = 1, you permit the transition to the energy-saving mode from the
PROFIdrive operating state (S4)
You can also set
● p5611.1 = 1: With the transition to the energy-saving mode, the inverter issues an OFF1
command and enters the start-inhibit state (S1).
● p5611.1 = 0: You can use p5614 to interconnect a signal source that switches the inverter
off and places it in the start-inhibit state (S1).
PROFIenergy measured values
PROFIenergy
Measured value
ID
Name
34
Active power
166
Power factor
200
Active energy import
136
Current energy-saving mode
Interconnectable display of the PROFIenergy status
PROFIenergy energy-saving mode active
Accuracy
Unit
Domain
Class
1
12
W
1
12
1
2
11
Wh
SINAMICS source parameters
Number
Name
r0032
Active power smoothed
r0038
Smoothed power factor
r0039[1]
Energy accepted
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Range of
values
r2004
0 ... 1
-
Inverter with CU230P-2 Control Units