Commissioning

5.5 Changing settings

5.5
Changing settings
Procedure
To start commissioning the safety functions, proceed as follows:
1. Go online with STARTER
2. In STARTER, select the fail-safe functions.
3. Select "Change settings".
4. Define what the results of your commissioning should look like:
• If you are only using STO as
• If, in addition to STO you use other safety functions, then select the extended functions
Additional information on the basic and extended functions are provided on the following
pages of this section.
You have completed the following commissioning steps:
● You have started to commission the safety functions.
● You have decided to use either the basic functions or the extended functions.
86
Parameter
Description
p0010 = 95
Drive commissioning parameter filter
Safety Integrated commissioning
p9761
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 ... FFFF FFFF.
p9762
New password
p9763
Confirm password
safety function of the inverter,
select the basic functions
with the interface that matches
your particular application.
with the interface that matches your particular application.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA