Backing up data and series commissioning
9.1 Backing up and transferring settings using a memory card
Procedure
Proceed as follows to transfer settings from a memory card to the inverter:
328
1. Go online with STARTER, and in your drive, select the "Drive Navigator".
2. Select the "Commissioning" button.
3. Select the button to transfer the data from the memory card to the inverter.
4. Select the settings as shown in the diagram and start the data backup.
5. Close the screen forms.
6. Go offline with STARTER.
7. Switch off the inverter power supply.
8. Wait until all LED on the inverter go dark.
9. Switch on the inverter power supply again.
Your settings become effective after this power-on reset.