Number
Cause
F13100
Know-how protection: Copy
protection error
F13101
Know-how protection: Copy
protection cannot be activated
F30001
Overcurrent
F30002
DC-link voltage overvoltage
F30003
DC-link voltage undervoltage
F30004
Inverter overtemperature
F30005
I2t inverter overload
F30011
Line phase failure
F30015
Motor cable phase failure
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Remedy
The know-how protection and the copy protection for the memory card
are active. An error occurred when checking the memory card.
Insert a suitable memory card and switch the inverter supply voltage
•
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
•
Insert a valid memory card.
Check the following:
Motor data, if required, carry out commissioning
•
Motor connection method (Υ / Δ)
•
U/f operation: Assignment of rated currents of motor and Power
•
Module
Line quality
•
Make sure that the line commutating reactor is connected properly
•
Power cable connections
•
Power cables for short-circuit or ground fault
•
Power cable length
•
Line phases
•
If this doesn't help:
U/f operation: Increase the acceleration ramp
•
Reduce the load
•
Replace the power unit
•
Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC-link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
Check the line voltage (p0210).
Check whether the inverter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
Check the rated currents of the motor and Power Module.
Reduce the current limit p0640.
When operating with U/f characteristic: Reduce p1341.
Check the inverter's input fuses.
Check the motor feeder cables.
Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).