Advertisement

Technical data
12.1 Technical data for CU230P-2
Feature
Analog inputs
Digital outputs /relay
outputs
Analog outputs
Motor temperature sensor PTC
USB interface
Dimensions (WxHxD)
Memory card (optional)
Weight
Operating temperature
Storage temperature
Relative humidity
1)
The following applies to systems complying with UL: A maximum of 3 A 30 VDC or 2 A 250 VAC may be connected via
terminals 18 / 20 (DO 0 NC) and 23 / 25 (DO 2 NC).
Note
Short-term voltage dips in the external 24 V supply (≤ 3 ms and ≤ 95% of the rated voltage)
If the 400 V supply of the inverter is switched off, the inverter reacts to short-term voltage
dips in the external 24 V supply with fault F30074. Communication via fieldbus, however,
remains in effect in this case.
374
Data / explanation
4 (AI 0 ... AI 3)
3 (DO 0 ... DO 2)
2 (AO 0 ... AO 1)
KTY84
Temperature switch with isolated contact
Mini-B
73mm × 199mm × 50mm
SINAMICS SD card,
512 MB
0.61kg
0 °C ... 60 °C
0 °C ... 50 °C
Observe any possible restrictions regarding the operating temperature as a result of the Power
Module.
- 40 °C ... 70 °C
< 95%
Differential inputs
12-bit resolution
13 ms response time
AI2 and AI3 can be switched:
0 V ... 10 V, 0 mA ... 20 mA or -10 V ... +10 V
Temperature sensor Pt1000/LG-Ni1000
If AI 0 and AI 1 are configured as supplementary digital
inputs: Low < 1.6 V, high > 4.0 V,
13 ms ± 1 ms response time for a debounce time p0724 = 0.
• DO 0, DO 2: 30 VDC 5 A / 250 VAC, 2 A
• DO 1:
30 VDC 0.5A
Update time: 2ms
0 V ... 10 V or 0 mA ... 20 mA
Reference potential: "GND"
16-bit resolution
4 ms update time
Short-circuit monitoring < 20Ω
Overtemperature 1650Ω
Short-circuit monitoring < 50 Ω
Wire breakage: > 2120Ω
Depth when mounting on the Power Module
Recommendation: 6SL3054-4AG00-2AA0
SDHC cards are not possible (SD High Capacity).
For operation without inserted operator panel.
For operation with inserted operator panel.
Condensation is not permissible.
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG