Setting examples of the condition data

The following shows setting examples of Condition data.
Example 1
This example uses the on/off state of a device as a condition.
• [Condition] Device XC (= Axis 1 BUSY signal) is off.
[Da.15] Condition target
[Da.16] Condition
operator
01H: Device X
08H: DEV = OFF
Example 2
This example uses a numerical value stored in the buffer memory as a condition.
• [Condition] The value stored in the buffer memory addresses 800, 801 (= [Md.20] Current feed value) is 1000 or larger.
[Da.15] Condition target
[Da.16] Condition
operator
04H: **  P1
04H: Buffer memory (2
words)
Example 3
This example specifies an axis and the positioning data No. of the axis as the target for the simultaneous start.
• [Condition] The positioning data No.3 of the axis 2 is the target for the simultaneous start.
[Da.15] Condition target
[Da.16] Condition
operator
05H: Positioning data No.
20H: Axis 2 specification
*1 Set 0000H for the starting axis (Axis which has executed the positioning start).
[Da.17] Address
[Da.18] Parameter 1
0CH
[Da.17] Address
[Da.18] Parameter 1
800
1000
[Da.17] Address
[Da.18] Parameter 1
0003H in the upper 16 bits
[Da.19] Parameter 2
[Da.19] Parameter 2
[Da.19] Parameter 2
*1
*1
4 ADVANCED POSITIONING CONTROL
4.4 Setting the Condition Data
4
169